Characteristics

Application domain
for electrical networks
Measured value
power quality, harmonic
Configuration
portable
Other characteristics
with data logger

Description

The MI 2883 Energy Master is a hand-held three phase power quality analyser, specially designed for energy logging and subsequently efficiency calculation.

MEASURING FUNCTIONS
• Voltage: TRMS, peak, crest factor (3-channel)
• Current: TRMS, peak, crest factor (4-channel)
• Power (active, reactive, apparent)
• Power measurements fully compliant with IEEE 1459 (active, non active, fundamen­tal, harmonic, load unbalance) and classic (vector or arithmetic) method
• Unbalance, flicker measurement
• Harmonic and interharmonic analysis up to 50th harmonics THD and TDD measurement
• Energy (active, reactive, generated, consumed)
• Capturing and recording of power supply events (shutdowns, interruptions, swells, dips)
• Power quality analysis according to EN 50160
• Recording up to 7 adjustable alarms
• Temperature measurement
• Power factor cos fi and tg fi

KEY FEATURES
• 3-voltage channels with wide measurement range: 0 … 1000 Vrms (CAT III / 1000 V)
• 4-current channels with support for automatic clamp recognition and “on instrument“ range selection
• Automatic Smart Clamp detection and Smart Clamp range selection
• Compliance with power quality standard IEC 61000-4-30 Class S
• Complete power quality analysis according to EN 50160 including signalling and interharmonics
• Support for microSD memory card (8-GB supplied with the instrument) up to 32GB
• Color-coded input terminals and termi¬nal labels to suit your application region
• Intuitive main menu and large icons that makes the equipment very easy to navigate and configure
• Current clamp auto range selection