Characteristics

Test type
high-voltage, VLF
Tested product
cable
Configuration
portable, compact

Description

The HVA34-1 and HVA34TD-1 are truly compact and portable VLF test sets which determine the condition of medium voltage cables.
HVA34TD-1 device includes integrated Tan Delta diagnostics capabilities and features TD leakage current correction (guard terminal), in comparison to HVA34-1 device, which can be with the TD diagnostics unit extended.
They both perform VLF and DC testing, as well as sheath testing with sheath fault location mode.

Performance: Outstanding features in terms of size, weight (39 kg) and performance (max. 10 µF).

Duty cycle: Operating time of these gadgets is not thermally limited; they may operate continuously.

Safety: The test sets have two independent earthing devices (electronic and mechanical discharging) and an integrated 12 kV transient protection system (at 50 Hz) to protect both the operator and the device.

Field use: A watertight and very rugged case with protection class of IP67 (with closed lid) makes no need for additional transport solutions.

Connectivity: On site, no external PC is needed. All results can be later downloaded via USB or Bluetooth for further investigation and easy reporting via software tool.

Service and maintenance: With no oil or arcing contacts, the dry-type transformer makes these gadgets almost maintenance-free.

MWT: In addition, HVA34TD-1 offers a Monitored Withstand Test, a combination of withstand testing and Tan Delta diagnostics in compliance with the guide IEEE 400.2-2013.

Output voltage – 34 kV, 24 kVrms
Output load – 1.5 μF @ 0.1 Hz @ 24 kVrms
Weight – 39 kg / 86 lbs